Symmetra PX

Xem thêm


Technical specifications

UPS Rating kVA/KW (PF = 1) 48kW
Mains Input (Normal Operation)
Grid system 3 phases + neutral + ground
Voltage range (full load) 340-477V
Frequency range 40-70Hz with 10 Hz/sec slew rate
Power factor (PF) >0.98 @ load > 50%
I thd < 5%
Nominal input current 77A @ 380V, 73A @ 400V, or 70A @ 415V
Maximum input current

(Nominal Vin, 10% charging batteries)

84.4A @ 380V, 80.2A @ 400V, or 77.3A @415V
Input current limit 98.3A @ 380V / 400V / 415V
Maximum input short-circuit level 30kA
Protection Backfeed contactor
Bypass Input (Bypass operation)
Grid system 3 phases + neutral + ground
Voltage (nominal) 380V / 400V / 415V
Voltage (range) +/-10% (from selected voltage)
Frequency (nominal) 50/60Hz
Frequency (range) +/-0.1Hz, +/-3Hz, +/-10Hz (user selectable)
Nominal input current 73A @ 380V; 69A @ 400V; 67A @ 415V
Maximum overload input current 84.4A @ 380V; 80.2A @ 400V; 77.3A @ 415V
Output
Power rating 48kW
Grid system 3 phases + neutral + ground
Voltage (nominal) 380V / 400V / 415V L-L
Output current (nominal) 73A @ 380; 69A @ 400V; 67A @ 415V
Maximum battery operation time Unlimited
Frequency regulation 50/60Hz bypass synchronized, 50/60Hz +/-0.1% free running
Synchronized slew rate Programmable to 0.25, 0.5, 1, 2, 4, 6Hz/sec
Overload (normal and battery operation) 150% for 60 seconds, 125% for 10 min, 100% continuous
V thd < 2% from 0 to 100% linear load, < 6% full non-linear load according to IEC/EN62040-3
Load PF from 0.5 leading to 0.5 lagging without any derating
Efficiency
Normal operation ≥ 95% at 35% – 100% load; ≥90% @ 15% – 34% load
Battery operation ≥ 94% at 25% – 100% load; ≥90% @ 15% – 34% load
Mechanical
Maximum dimensions (HxWxD) 1991 x 600 x 1070mm
Net weight 796kg
Shipping weight 858kg
UPS Frame Maximum Capacity
16kW power modules 3
Battery modules 4
Power distribution modules 6
Regulatory Compliance
CE, UL1778, EN/IEC62040-1-1, EN/IEC/UL60950-1, EN50091-2 / IEC62040-2 (class A), FCC15A, EN/IEC62040-3

 

UPS Rating kVA/kW (PF=1) 250 kW 500 kW
Mains Input (Normal Operation)
Grid system Single feed: 3 phases + neutral + ground, 3 phases + ground Dual feed: 3 phases + ground
Grid parallel system Single feed: 3 phases + neutral + ground Dual feed: 3 phases + ground
Voltage range +/- 15% for full performance; 340 – 460 V at 400 V (408 – 552 V at 480 V)
Frequency range 40-70 Hz with 10 Hz/sec slew rate
Power factor (PF) >0.995 at load = 100%

>0.99 at load > 50%

>0.97 at load > 25%

I thd (full load) < 5%
Nominal input current 378 A @ 400 V

(315 A @ 480 V)

756 A @ 400 V

(630 @ 480 V)

Maximum input current

(Nominal Vin, 10 % charging batts)

416 A @ 400 V

(346 A @ 480 V)

831 A @ 400 V

(693 A @ 480 V)

Input current limit 447 A @ 400 V

(372 A @ 480 V)

894 A @ 400 V

(745 A @ 480 V)

Maximum input short-circuit level 65 kA (50 kA with standard MBwD)
Protection Backfeed contactor
Output
Power rating 250 kW 500 kW
Grid system 3 phases + neutral + ground, 3 phases + ground
Voltage nominal 380 V / 400 V / 415 V / 480 V L-L
Nominal output current 361 A @ 400 V

(301 A @ 480 V)

722 A @ 400 V

(601 A @ 480 V)

Maximum battery operation time Unlimited
Frequency regulation 50/60 Hz bypass synchronized, 50/60 Hz +/-0.1% free running
Synchronized slew rate Programmable to 0.25, 0.5, 1, 2, 4, 6 Hz/sec
Overload (normal and battery operation) 150% for 30 seconds, 125% for 10 min, 100% continuous
V thd < 2% from 0 to 100% linear load, < 6% full non-linear load according to IEC/EN62040-3
Load PF from 0.5 leading to 0.5 lagging without any derating
Bypass Input (Bypass operation)
Grid system Single feed: 3 phases + neutral + ground, 3 phases + ground. Dual feed: 3 phases + ground
Voltage (nominal) 380 V / 400 V / 415 V / 480 V L-L
Voltage (range) +/-10% (from selected voltage)
Frequency (nominal) 50/60 Hz
Frequency (range) +/-0.5%, +/-1%, +/-2%, +/-4%, +/-6% and +/-8% (user selectable)
Nominal input current 361 A @ 400 V

(301 A @ 480 V)

722 A @ 400 V

(601 A @ 480 V)

Maximum overload input current 397 A @ 400 V

(376 A @ 480 V)

794 A @ 400 V

(752 A @ 480 V)

Efficiency
Normal operation > 96% at 35% – 100% load
Battery operation > 96% at 35% – 100% load
Mechanical: Stand-alone UPS, no batteries
Size (H x W x D) 1991 x 1600 x 1070 mm

(78.7 x 63 x 42.1 in)

1991 x 2200 x 1070 mm

(78.7 x 86.6 x 42.1 in)

Weight 4509 kg (9940 lb) 8336 kg (18377 lb)
Mechanical: UPS with MBwD and 6 min. battery runtime
Size (H x W x D) 1991 x 3100 x 1070 mm

(78.7 x 121.9 x 42.1 in)

1991 x 5200 x 1070 mm

(78.7 x 204.7 x 42.1 in)

Weight 1057 kg (2330 lb) 1722 kg (3797 lb)
Environmental
Storage temperature, UPS only -30 to 70°C (-22° to 158°F)
Storage temperature, UPS and batteries -15 to 40°C (5 to 104°F) Battery self discharge: approximately 6 -8 months @25°C; 1-2 months @45°C
Operating temperature* 0 to 40°C (32 to 104°F)
Regulatory compliance UL Listed, ULc Listed, CE, EN/IEC 62040-2 (class A), FCC part 15, EN/IEC 62040-3, EN/IEC 62040-1-1, UL 1778, UL 60950-1, CSA C22.2 No. 107.3-05