Symmetra PX 48 kW: Scalable from 16 to 48 kW

Technical specifications

 

Rated power (kVA/kW)                                                                                                           48 kw

Mains input (Normal operation)

Grid system

3 phases + neutral + ground

Voltage range (full load)

340 – 477 V

Frequency range

40 – 70 Hz with 10 Hz/sec slew rate

Power factor (PF)

>0.98 @ load > 50%

I thd

< 5%

Nominal input current

77 A @ 380 V, 73 A @ 400 V, or 70 A @ 415 V

Maximum input current

(Nominal Vin, 10% charging batteries)

 

84.4 A @ 380 V, 80.2 A @ 400 V, or 77.3 A @ 415 V

Input current limit

98.3 A @ 380 V/400 V/415 V

Maximum input short-circuit level

30 kA

Protection

Backfeed contactor

Bypass input (Bypass operation)

Grid system

3 phases + neutral + ground

Voltage (nominal)

380 V/400 V/415 V

Voltage (range)

+/-10% (from selected voltage)

Frequency (nominal)

50/60 Hz

Frequency (range)

+/-0.1 Hz, +/-3 Hz, +/-10 Hz (user selectable)

Nominal input current

73 A @ 380 V; 69 A @ 400 V; 67 A @ 415 V

Maximum overload input current

84.4 A @ 380 V; 80.2 A @ 400 V; 77.3 A @ 415 V

Output

Power rating

48 kW

Grid system

3 phases + neutral + ground

Voltage (nominal)

380 V/400 V/415 V L-L

Output Current (nominal)

73 A @ 380; 69 A @ 400 V; 67 A @ 415 V

Maximum battery operation time

Unlimited

Frequency regulation

50/60 Hz bypass synchronized, 50/60 Hz +/-0.1% free running

Synchronized slew rate

Programmable to 0.25, 0.5, 1, 2, 4, 6 Hz/sec

Overload (normal and battery operation)

150% for 60 seconds, 125% for 10 min, 100% continuous

V thd

< 2% from 0 to 100% linear load, < 6% full nonlinear load according to IEC/EN62040-3

Load PF

from 0.5 leading to 0.5 lagging without any derating

Efficiency

Normal operation

≥ 95% at 35% – 100% load; ≥90% @ 15% – 34% load

Battery operation

≥ 94% at 25% – 100% load; ≥90% @ 15% – 34% load

Mechanical

Maximum dimensions (HxWxD)

1991 x 600 x 1070 mm

Net weight

796 kg

Shipping weight

858 kg

UPS frame maximum capacity

16 kW power modules

3

Battery modules

4

Power distribution modules

6

Regulatory compliance