Easy UPS 3 (E3S, E3M)

Xem thêm

 

 

Easy UPS 3S technical specifications
Rated Power (kVA/kW) 10/10 15/15 20/20* 30/30* 40/40*
Normal AC supply input
Input voltage (V) 380/400/415 V (Three-phase + Neutral)
Frequency (Hz) 45 – 65 Hz
Input power factor >0.99
THDI <3% for 10 kVA UPS, <4% for 15-40 kVA UPS
Input voltage range 304V to 477V at full load
Dual mains input Yes (default: single mains input)
Output
Nominal output voltage (V) 3:1 – 220/230/240 V
3:3 – 380/400/415 V
Efficiency: Double conversion mode Up to 96%
Efficiency: ECO mode Up to 99%
Overload capacity in normal operation 130% for 10 minutes and 130-150% for one minute
Communication and management
Communication interface RS232, RS485, USB, dry contact, Modbus TCP/IP, optional network card
Control panel Multi-function LCD, status and display console
Weights and dimensions
UPS for external batteries, unpackaged/ shipping dimensions (H × W × D, mm) 530 × 250 × 700 mm/

772 × 400 × 857 mm

530 × 250 × 700 mm/

772 × 400 × 857 mm

770 × 250 × 800 mm/

1015 × 400 × 982 mm

770 × 250 × 800 mm/

1015 × 400 × 982 mm

770 × 250 × 900 mm/

1015 × 400 × 1050 mm

UPS for internal batteries, without batteries, unpackaged, shipping

dimensions (H x W x D, mm)

1400 × 380 × 928 mm/

1640 × 563 × 1014 mm

1400 × 380 × 928 mm/

1640 × 563 × 1014 mm

1400 × 380 × 928 mm/

1640 × 563 × 1014 mm

1400 × 500 × 969 mm/

1640 × 683 × 1114 mm

1400 × 500 × 969 mm/

1640 × 683 × 1114 mm

UPS for external batteries, unpackaged/shipping weight (kg) 36/50 36/50 58/75 60/77 70/86
UPS for internal batteries, without batteries, unpackaged/shipping weight (kg) 112/145 112/145 122/158 152/190 158/195
Battery string (1 string/4 modules), unpackaged/shipping weight (kg) 27 kg per module/28 kg per module
Regulatory
Safety IEC/EN62040-1-1 Performance IEC 62040-3
EMC/EMI/RFI IEC 62040-2 Environmental IEC 62040-4
Markings CE.RCM, EAC, WEEE
Battery type
Battery type VRLA
Nominal DC bus (100% load) +/-192 to +/-240
Charging power in % of output power (selectable) 1-20%
Environmental
Operating temperature 0°C to 40°C
Relative humidity 0 to 95% non-condensing
Operating elevation 0 to 1,000 m at 100% load
Audible noise at 1m from unit 10-20 kVA: 60 dBA at 100% load; 30-40 kVA: 63 dBA at 100% load
Protection class IP20
Warranty One year with Schneider Electric-certified Field Service Representative or Certified Service Partner Start-up Service (sold separately)

 

Easy UPS 3M technical specifications
Rated Power (kVA/kW) 60/60 80/80 100/100 120/120 160/160 200/200
Normal AC supply input
Input voltage (V) 380/400/415 V (Three-phase + Neutral + PE)
Frequency (Hz) 40–70 Hz
Input power factor >0.99
THDI <3% at full linear load
Input voltage range 342 V to 477 V at full load at 40°C**
Dual mains input Yes (default: single mains input)
Output
Nominal output voltage (V) 3:3 – 380/400/415 V
Efficiency: Double conversion mode Up to 95.5%
Efficiency: ECO mode Up to 99%
Overload capacity in normal operation 125% for 10 minutes, 150% for 1 minute*
Communication and management
Communication interface RS485, USB, Dry contact, Modbus TCP/IP (SNMP optional)
Control panel Five inch touchscreen LCD, status, and display console
Weights and dimensions
UPS for external batteries, unpackaged/ shipping

dimensions (H × W × D, mm)

915 × 360 × 850 mm/

1140 × 475 × 965 mm

915 × 360 × 850 mm/

1140 × 475 × 965 mm

915 × 360 × 850 mm/

1140 × 475 × 965 mm

1300 x 500 x 850 mm/

1500 x 625 x 975 mm

1300 x 500 x 850 mm/

1500 x 625 x 975 mm

1300 x 600 x 850 mm/

1500 x 725 x 975 mm

UPS for external batteries, unpackaged/shipping,

weights (kg)

109/133 140/164 145/169 193/223 227/257 304/338
Regulatory
Safety IEC/EN 62040-1 Performance IEC62040-3
EMC/EMI/RFI IEC 62040-2 Environmental IEC 62040-4
Markings CE TUV
Battery type
Battery type VRLA
Nominal DC Bus (100% load) +/-216 to +/-300
Charging power in % of output power (selectable) 60 kVA: 1-20%; 80 kVA: 1-30%; 100 kVA: 1-24%; 120 kVA: 1-20%; 160 kVA: 1-22.5%; 200 kVA: 1-24%
Environmental
Operating temperature 0 to 40°C
Relative humidity 0 to 95% non-condensing
Operating elevation 0 to 1,500 m at 100% load
Audible noise at 1m from unit 60-100 kVA: 65 dBA at 100% load*; 120-200 kVA: <70 dBA at 100% load*
Protection class IP20
*Under 30°C

**342–150 with a linear derating of the load to 30%

 

Xem thêm

,