🛒 SY400K500D

Symmetra PX 400kW Scalable to 500kW
without Maintenance Bypass or Distribution-Parallel Capable

Giá: (Liên hệ)

 

Thông số kỹ thuật

Overview
Description A high-performance, 3-phase, modular, scalable, power protection solution with industry-leading efficiency, capacity, and performance for medium to large data centers and mission-critical environments. Multiple UPSs can be installed in parallel for ultra-efficient system redundancy or up to 2MW of power protection. Parallel installations with custom switchgear and installations using a 3rd-party maintenance bypass panel require the APC Symmetra PX250/500 Third Party Switchgear Kit for breaker monitoring and EPO functionality.
Model Name Symmetra PX 400kW Scalable to 500kW without Maintenance Bypass or Distribution-Parallel Capable
Includes Assembly service , Installation guide , Network Management Card , Start-Up Service , User Manual
Product Distribution Albania , Algeria , Andorra , Angola , Anguilla , Antigua And Barbuda , Argentina , Armenia , Aruba , Australia , Austria , Azerbaijan , Bahrain , Bangladesh , Barbados , Belarus , Belgium , Belize , Benin , Bermuda , Bolivia , Bosnia And Herzegovina , Botswana , Brazil , Bulgaria , Burkina Faso , Burundi , Cameroon , Canada , Cayman Islands , Central African Republic , Chad , Chile , China , Colombia , Congo , CONGO, THE DEMOCRATIC REPUBLIC OF THE , Costa Rica , Cote D’Ivoire , Croatia , Cuba , Cyprus , Czech Republic , Denmark , Djibouti , Dominican Republic , Ecuador , Egypt , El Salvador , Equatorial Guinea , Eritrea , Estonia , Ethiopia , Falkland Islands (Malvinas) , Finland , France , Gabon , Gambia , Georgia , Germany , Ghana , Gibraltar , Greece , Guatemala , Guinea , Guyana , Honduras , Hong Kong , Hungary , Iceland , India , Indonesia , Iran (Islamic Republic Of) , Iraq , Ireland , Israel , Italy , Jamaica , Jordan , Kazakhstan , Kenya , KOREA, REPUBLIC OF , Kuwait , Latvia , Lebanon , Lesotho , Liberia , Liechtenstein , Lithuania , Luxembourg , Macedonia , Malawi , Malaysia , Mali , Malta , Mauritania , Mexico , Moldova, Republic Of , Mongolia , Morocco , Mozambique , Namibia , Netherlands , Netherlands Antilles , New Zealand , Nicaragua , Niger , Nigeria , Norway , Oman , Pakistan , Panama , Paraguay , Peru , Philippines , Poland , Portugal , Puerto Rico , Romania , Russian Federation , Rwanda , Saudi Arabia , Senegal , Sierra Leone , Singapore , Slovakia (Slovak Republic) , Slovenia , Somalia , South Africa , Spain , Sri Lanka , Sudan , Suriname , Sweden , Switzerland , Taiwan , Tajikistan , TANZANIA, UNITED REPUBLIC OF , Thailand , Togo , Trinidad And Tobago , Tunisia , Turkey , Turkmenistan , Uganda , Ukraine , United Arab Emirates , United States , Uruguay , Uzbekistan , Venezuela , Viet Nam , VIRGIN ISLANDS (UNITED STATES) , Western Sahara , Yemen , Zambia , Zimbabwe
General
Bypass Voltage Tolerance +/-10% settable from +/-4/6/8 and 10%
Output
Output Power Capacity 400.0 KW / 400.0 kVA
Max Configurable Power (Watts) 500.0 KW / 500.0 kVA
Nominal Output Voltage 400 3PH , 480 3PH
Output Voltage Distortion Less than 2%
Output Frequency (sync to mains) 50 Hz , 60 Hz
Other Output Voltages 415V
Double Conversion Online
Waveform Type Sine wave
Output Connections (1) Hard Wire 4-wire (3PH + G) (Battery Backup) , (1) Hard Wire 5-wire (3PH + N + G) (Battery Backup)
Output Voltage Tolerance +/-1% static and +/- 5% at 100% load step
Output Voltage THD < 2% for 0 to 100% linear load and < 6% for full non linear load
Overload Operation 10 minutes @ 125% and 30 seconds @ 150%
Bypass Built-in Static Bypass
Input
Nominal Input Voltage 400 3PH
480 3PH
Input Frequency 40 – 70 Hz (auto sensing)
Input Connections Hard Wire 4-wire (3PH + G) , Hard Wire 5-wire (3PH + N + G)
Input voltage range for main operations 340 – 460 (400V) V , 408 – 552 (480) V
Other Input Voltages 415
Maximum Short Circuit Withstand (Icw) 50
Input Total Harmonic Distortion Less than 5% for full load
Type of Input Protection Required 3-pole breaker
Batteries & Runtime
Battery Type VRLA
Included Battery Modules 26
Battery Slots Empty 36
Typical recharge time 3.5 hour(s)
RBC Quantity 6
Efficiency in Battery Operation 96.00%
Overload Operation 10 minutes @ 125% and 60 seconds @ 150%
Communications & Management
Interface Port(s) SYPX250-500_Parallel
Available SmartSlot™ Interface Quantity 1
Pre-Installed SmartSlot™ Cards AP9635
Control panel Touch Screen LCD User Interface
Emergency Power Off (EPO) Optional
Physical
Maximum Height 1991.0 mm
Maximum Width 4200.0 mm
Maximum Depth 1070.0 mm
Net Weight 6829.0 kg
Shipping Weight 7493.0 kg
Shipping Height 2150.0 mm
Shipping Width 7100.0 mm
Shipping Depth 1270.0 mm
Color Black
Environmental
Operating Environment 0 – 40 °C
Operating Relative Humidity 0 – 95 %
Operating Elevation 0-999.9 meters
Storage Temperature -15 – 40 °C
Storage Relative Humidity 0 – 95 %
Storage Elevation 0-15000 meters
Audible noise at 1 meter from surface of unit 54.000 dB
Online Thermal Dissipation 49515.000 BTU/hr
Protection Class IP 20 , NEMA 1
Conformance
Approvals CSA C22.2 No.107.3-05 , EN/IEC 62040-1-1 , EN/IEC 62040-2 , EN/IEC 62040-3 , Eurobat General Purpose , UL 1778 , UL 60950-1 , UL Listed , cUL Listed
Standard warranty 1 year on-site repair or replace with factory authorized Start-Up