Easy UPS 3 (E3S, E3M)
Easy UPS 3S technical specifications | |||||
Rated Power (kVA/kW) | 10/10 | 15/15 | 20/20* | 30/30* | 40/40* |
Normal AC supply input | |||||
Input voltage (V) | 380/400/415 V (Three-phase + Neutral) | ||||
Frequency (Hz) | 45 – 65 Hz | ||||
Input power factor | >0.99 | ||||
THDI | <3% for 10 kVA UPS, <4% for 15-40 kVA UPS | ||||
Input voltage range | 304V to 477V at full load | ||||
Dual mains input | Yes (default: single mains input) | ||||
Output | |||||
Nominal output voltage (V) | 3:1 – 220/230/240 V | ||||
3:3 – 380/400/415 V | |||||
Efficiency: Double conversion mode | Up to 96% | ||||
Efficiency: ECO mode | Up to 99% | ||||
Overload capacity in normal operation | 130% for 10 minutes and 130-150% for one minute | ||||
Communication and management | |||||
Communication interface | RS232, RS485, USB, dry contact, Modbus TCP/IP, optional network card | ||||
Control panel | Multi-function LCD, status and display console | ||||
Weights and dimensions | |||||
UPS for external batteries, unpackaged/ shipping dimensions (H × W × D, mm) | 530 × 250 × 700 mm/
772 × 400 × 857 mm |
530 × 250 × 700 mm/
772 × 400 × 857 mm |
770 × 250 × 800 mm/
1015 × 400 × 982 mm |
770 × 250 × 800 mm/
1015 × 400 × 982 mm |
770 × 250 × 900 mm/
1015 × 400 × 1050 mm |
UPS for internal batteries, without batteries, unpackaged, shipping
dimensions (H x W x D, mm) |
1400 × 380 × 928 mm/
1640 × 563 × 1014 mm |
1400 × 380 × 928 mm/
1640 × 563 × 1014 mm |
1400 × 380 × 928 mm/
1640 × 563 × 1014 mm |
1400 × 500 × 969 mm/
1640 × 683 × 1114 mm |
1400 × 500 × 969 mm/
1640 × 683 × 1114 mm |
UPS for external batteries, unpackaged/shipping weight (kg) | 36/50 | 36/50 | 58/75 | 60/77 | 70/86 |
UPS for internal batteries, without batteries, unpackaged/shipping weight (kg) | 112/145 | 112/145 | 122/158 | 152/190 | 158/195 |
Battery string (1 string/4 modules), unpackaged/shipping weight (kg) | 27 kg per module/28 kg per module | ||||
Regulatory | |||||
Safety | IEC/EN62040-1-1 | Performance | IEC 62040-3 | ||
EMC/EMI/RFI | IEC 62040-2 | Environmental | IEC 62040-4 | ||
Markings | CE.RCM, EAC, WEEE | ||||
Battery type | |||||
Battery type | VRLA | ||||
Nominal DC bus (100% load) | +/-192 to +/-240 | ||||
Charging power in % of output power (selectable) | 1-20% | ||||
Environmental | |||||
Operating temperature | 0°C to 40°C | ||||
Relative humidity | 0 to 95% non-condensing | ||||
Operating elevation | 0 to 1,000 m at 100% load | ||||
Audible noise at 1m from unit | 10-20 kVA: 60 dBA at 100% load; 30-40 kVA: 63 dBA at 100% load | ||||
Protection class | IP20 | ||||
Warranty | One year with Schneider Electric-certified Field Service Representative or Certified Service Partner Start-up Service (sold separately) |
Easy UPS 3M technical specifications | ||||||
Rated Power (kVA/kW) | 60/60 | 80/80 | 100/100 | 120/120 | 160/160 | 200/200 |
Normal AC supply input | ||||||
Input voltage (V) | 380/400/415 V (Three-phase + Neutral + PE) | |||||
Frequency (Hz) | 40–70 Hz | |||||
Input power factor | >0.99 | |||||
THDI | <3% at full linear load | |||||
Input voltage range | 342 V to 477 V at full load at 40°C** | |||||
Dual mains input | Yes (default: single mains input) | |||||
Output | ||||||
Nominal output voltage (V) | 3:3 – 380/400/415 V | |||||
Efficiency: Double conversion mode | Up to 95.5% | |||||
Efficiency: ECO mode | Up to 99% | |||||
Overload capacity in normal operation | 125% for 10 minutes, 150% for 1 minute* | |||||
Communication and management | ||||||
Communication interface | RS485, USB, Dry contact, Modbus TCP/IP (SNMP optional) | |||||
Control panel | Five inch touchscreen LCD, status, and display console | |||||
Weights and dimensions | ||||||
UPS for external batteries, unpackaged/ shipping
dimensions (H × W × D, mm) |
915 × 360 × 850 mm/
1140 × 475 × 965 mm |
915 × 360 × 850 mm/
1140 × 475 × 965 mm |
915 × 360 × 850 mm/
1140 × 475 × 965 mm |
1300 x 500 x 850 mm/
1500 x 625 x 975 mm |
1300 x 500 x 850 mm/
1500 x 625 x 975 mm |
1300 x 600 x 850 mm/
1500 x 725 x 975 mm |
UPS for external batteries, unpackaged/shipping,
weights (kg) |
109/133 | 140/164 | 145/169 | 193/223 | 227/257 | 304/338 |
Regulatory | ||||||
Safety | IEC/EN 62040-1 | Performance | IEC62040-3 | |||
EMC/EMI/RFI | IEC 62040-2 | Environmental | IEC 62040-4 | |||
Markings | CE TUV | |||||
Battery type | ||||||
Battery type | VRLA | |||||
Nominal DC Bus (100% load) | +/-216 to +/-300 | |||||
Charging power in % of output power (selectable) | 60 kVA: 1-20%; 80 kVA: 1-30%; 100 kVA: 1-24%; 120 kVA: 1-20%; 160 kVA: 1-22.5%; 200 kVA: 1-24% | |||||
Environmental | ||||||
Operating temperature | 0 to 40°C | |||||
Relative humidity | 0 to 95% non-condensing | |||||
Operating elevation | 0 to 1,500 m at 100% load | |||||
Audible noise at 1m from unit | 60-100 kVA: 65 dBA at 100% load*; 120-200 kVA: <70 dBA at 100% load* | |||||
Protection class | IP20 | |||||
*Under 30°C
**342–150 with a linear derating of the load to 30% |